Mohammad Reza Haseli, Farhad Haghjoo, Abbas Hasani

A new air gap flux‐based technique to detect loss of field in synchronous generators

  • Electrical and Electronic Engineering

AbstractA new technique is proposed for loss of field (LOF) detection in synchronous generators (SGs). The proposed scheme employs the variations of SG angular velocity ∆ωφ and load angle ∆δφ to reach this goal, while the mentioned parameters are estimated through air gap flux estimation. The proposed scheme performance is evaluated using realistic simulation case studies based on IEEE C. 37. 102 standard compared to the conventional impedance‐based one. The obtained results show that the presented scheme excels the conventional scheme from speed and security viewpoints. Moreover, the estimation procedure of ∆ωφ and ∆δφ is experimentally validated by using a 10 kVA SG and the results demonstrate that the proposed technique can be easily set and implemented.