Sub-Synchronous and Super-Synchronous Oscillation Propagation in Offshore Wind Farms with Hybrid DRU MMC HVDC Transmission

Xiaofei Chang, Yi Lu, Feng Xu, Jiachuan You, Ziming Li, Wei Chen, Qi Zhang, Xiangyuan Zhang, Qing Chen, Bin Hu, Heng Nian

Hybrid high-voltage direct-current (HVDC) transmission using a diode rectifier unit (DRU) and a modular multilevel converter (MMC) reduces the required capacity of the controllable offshore converter. However, the different terminal controls and AC/DC frequency coupling complicate the assessment of oscillation propagation. This paper presents an impedance-based framework for voltage and current propagation in an offshore wind farm connected through an AC-parallel/DC-series DRU-MMC link. The receiving-end MMC impedance is combined with the series DC network and incorporated into the sending-end hybrid-converter model. Four amplitude ratios characterize AC-to-DC and DC-to-AC propagation while retaining the coupled AC sidebands. In a 1000 MW, 500 kV simulation case, a power increase from 0.4 to 0.5 p.u. produces AC components at 8.3 and 91.7 Hz and a corresponding DC component at 41.7 Hz. With the two AC voltage amplitudes combined by their root-sum-square (RSS), the sending-end AC-to-DC, DC-network, and receiving-end DC-to-AC voltage–amplitude ratios calculated from the reported FFT amplitudes are 0.1474 (−16.63 dB), 0.7648 (−2.33 dB), and 0.2373 (−12.50 dB), respectively. These results support the predicted attenuation trend along the AC–DC–AC path and provide a basis for coordinated terminal monitoring and further damping analysis.