Probabilistic Risk Assessment of Grid-Scale Lithium-Ion Battery Energy Storage System Fire Hazards: Hydrogen Fluoride (HF) Toxicity, Suppression Effectiveness, and Comparative Compartment Design Analysis
Samson Tan, Teik Toe Teoh, Paul Joseph, Khalid MoinuddinBattery Energy Storage Systems (BESS), utilising chemistries based on Nickel Manganese Cobalt (NMC) containing lithium-ion devices, often present fire safety hazards that existing qualitative risk frameworks, including NFPA 855’s 5 × 5 consequence-likelihood matrix, are insufficiently granular to quantify. This paper presents an original probabilistic risk assessment (PRA) of fire hazards associated with BESS for a 485.52 kWh NMC installation at the Equinix SG4-4A data centre in Singapore, using Monte Carlo simulation (N = 10,000 iterations) to characterise uncertainty in hydrogen fluoride (HF) gas dose, time to Immediately Dangerous to Life or Health (IDLH) concentration, cabinet-to-cabinet propagation probability, and suppression effectiveness. The HF yield is modelled as a triangular distribution (0.3–0.8 g/kWh, mode 0.5 g/kWh), ventilation activation delay as log-normal (median 90 s), and suppression effectiveness as a piecewise function of water application delay. The results demonstrated that HF dose exceeded the National Institute for Occupational Safety and Health (NIOSH) IDLH of 25 mg/m3 in 100% of simulated scenarios for both single- and two-compartment designs, thus confirming that threshold HF toxicity was essentially unavoidable for any occupant present during a full thermal runaway event, and that ventilation alone cannot achieve adequate risk reduction. The single-stage suppression effectiveness was found to be only 37.9% (mean), providing quantitative confirmation that two-stage (clean agent + water) suppression is warranted for NMC chemistry. The two-compartment design was found to reduce the peak HF dose by 50%, and also reduced the mean IDLH clearance time from 599 to 301 min, thus shifting residual risk from As Low As Reasonably Practicable (ALARP)-tolerable to broadly acceptable under UK Health and Safety Executive (HSE) criteria. The paper proposes a quantitative PRA framework as a complement to NFPA 855 Chapter 5’s qualitative Hazard Mitigation Analysis, enabling more informed engineering decisions for BESS fire safety. To the best of our knowledge, this is the first study to apply Monte Carlo simulation to HF dose modelling in a tropical data-centre BESS context and thereby address a documented gap in the literature.