DOI: 10.3390/buildings16214239 ISSN: 2075-5309

Parametric Study of Wet-Spray Regeneration for Dust-Loaded Micro-Electrostatic Precipitators in Residential Ventilation

Haoyang Huang, Chenrui Gong, Yunzhi Ling, Clement Ndubuisi Ezeifedikwa, Abdulmalik Mohammed Abu, Junming Zhou, Xiaofeng Niu

Particle accumulation increases the pressure drop and reduces the long-term performance of micro-electrostatic precipitators (MESPs). This study quantifies wet-spray regeneration responses for a single MESP geometry intended for residential ventilation. The effects of spray pressure, spray angle, nozzle-to-module distance, and washing duration were evaluated using single-factor and orthogonal experiments. Increasing the spray pressure from 0.1 to 0.3 MPa decreased the post-cleaning pressure drop from 38.5 to 16.5 Pa and increased the pressure recovery rate from 54.9% to 95.3%, while further increases produced diminishing benefits. The operating ranges identified for nozzle-to-module distance and washing duration were 50–100 mm and 20–30 s, respectively. Within the selected factor levels, the factor order was nozzle-to-module distance > spray pressure > washing duration > spray angle. The preferred parameter combination identified by orthogonal range analysis was 0.4 MPa, 30°, 50 mm, and 30 s, based on the factor-level means. This combination requires confirmation using the same module and dust-loading conditions. The numerical comparison gave a relative deviation of 5.5% at 0.3 MPa and provided flow-field context for the parameter trends. The findings link the four spray parameters to residual airflow resistance and post-cleaning particle-collection efficiency, providing operating data for residential MESP regeneration.