DOI: 10.3390/en19205018 ISSN: 1996-1073

Impulse Effective Length of Horizontal Grounding Electrodes for 220 kV Transmission Towers Under Different Soil Conditions

Hanjie Yuan, Liang Chen, Yu Deng, Yaohua Zheng, Limeng Dong, Guote Liu

This study used a CDEGS electromagnetic-transient model to examine the impulse effective length of a horizontal grounding electrode connected to a 220 kV cat-head transmission-tower system. The model included the tower, four foundations, two overhead ground wires, adjacent-tower paths, and a buried horizontal electrode. Effective length was defined using a 5° tangent-slope criterion applied to the impulse-grounding-resistance–length curve. For a negative-polarity impulse with a magnitude of 20 kA and an 8/20 μs waveform, the calculated effective lengths were 7.679, 16.5, and 24.985 m in homogeneous soils with resistivities of 10, 100, and 1000 Ω·m, respectively. Calculations over 20–150 kA indicated that, within the investigated cases, soil condition produced a larger variation in the shunt coefficient than current magnitude. Limited field measurements in layered soil showed a qualitatively similar diminishing-return trend, but the three tested electrode lengths were insufficient for a statistically robust three-parameter fit and were not used as a direct validation of the complete tower model. System-level calculations further indicated that increasing soil resistivity from 10 to 3000 Ω·m reduced the grounding-channel shunt coefficient and the calculated lightning withstand level for the specified line configuration. The reported effective lengths are criterion- and configuration-specific engineering estimates rather than universal design constants.