DOI: 10.3390/pr14213552 ISSN: 2227-9717

Grid State-Aware Adaptive Switching Between Grid-Following and Grid-Forming Modes Enabled by Fast Online Impedance Estimation

Yonghua Chen, Wei Du, Tian Gao, Jiaxing Lei, Wusen Wang

Changes in grid strength can impair the stability and dynamic performance of converters operated in fixed grid-following or grid-forming modes. Adapting the mode requires impedance estimation and preparation of the incoming controller. This paper proposes a single-converter strategy that combines impedance estimation using a notch–bandpass compound filter, hysteretic mode selection, and bidirectional controller state preparation. The estimator identifies resistance and inductance from the injected frequency response and reconstructs the fundamental frequency short-circuit ratio. The switching strategy coordinates grid strength requests with phase/amplitude synchronization and state initialization to reduce transfer transients. Conditional error and synchronization analyses establish the requirements linking estimation to mode execution. With matched measurement channels, 86 fixed-mode simulation configurations give a maximum final-interval short-circuit ratio error of 2.32 percent. In shared-input noiseless tests, the estimator has a median settling time of 130.85 milliseconds as measured from the network change command. At 20 kW, the converter peak current in a common transfer window from grid-following to grid-forming decreases from 217.41 to 45.83 A relative to direct transfer, a 78.9 percent reduction. These results support the proposed integration of online grid strength estimation and prepared mode transfer in the evaluated single-converter system.

More from our Archive