DOI: 10.3390/electronics15132790 ISSN: 2079-9292

Effectiveness of Fuzzy Logic Controller in Maintaining Stability of Digital Twin-Enabled Offshore Wind Farm (OWF) Integrated with HVDC Grid

Yamini Gaddam, Mohd. Hasan Ali

Offshore wind farms are increasingly and rapidly expanding due to their ability to harness strong and consistent wind energy resources. Large offshore wind farms are connected to mainland grids through High-Voltage Direct Current (HVDC) technology. However, offshore wind farms can often experience disturbances related to sudden wind changes, voltage drops/dips, faults related to converter switching, and unbalanced grid conditions which affect both the HVDC operation and wind turbine output. As a result, there is a growing need for more advanced and reliable modeling and monitoring tools. Moreover, traditional proportional-integral (PI) controllers are widely applied in wind turbines and HVDC systems due to their simple structure, easy implementation, and reliability. However, PI controllers perform poorly under non-linear and abnormal/fast-changing conditions, especially during sudden drops in wind power and grid faults. With this background, this paper first develops a digital twin model of an offshore wind farm that enables remote operation and monitoring of individual wind turbines. Also, an artificial intelligence (AI)-based controller, namely a fuzzy logic controller (FLC), is proposed to maintain transient stability of a full digital twin-based offshore wind farm connected to the HVDC grid under fault conditions. The effectiveness of the proposed FLC is demonstrated by considering a digital twin-enabled 700 MW offshore wind farm. The performance of the proposed FLC has been compared with that of the PI controller. Simulations performed by the MATLAB/Simulink software show that during the moderate voltage dip at 15 s, the PI controller experienced a 29.8% power reduction with a recovery time of approximately 9 s, whereas the FLC reduced the power drop to 23.1% and recovered within 6 s. During the severe converter disturbance at 15 s, the PI controller recorded a 36.9% power reduction compared to 23.4% for the FLC. Similarly, during the short-duration turbulence at 15 s, the PI controller exhibited a 36.73% power drop and recovered in approximately 7 s, while the FLC limited the power reduction to 19.17% and recovered within 5s. Overall, the FLC provided improved voltage stability, faster recovery, reduced oscillations, and superior fault ride-through capability compared with the conventional PI controller, demonstrating its effectiveness for digital twin-enabled offshore wind farm application.

More from our Archive