Active Symmetry Support Control for Grid-Following/Grid-Forming Hybrid Renewable Energy Stations Considering Transient Synchronization Stability
Zian Li, Lihua Wang, Ji Li, Yang Kou, Chaoran Yang, Pengtao WuAn active symmetry support control method based on model predictive control and incorporating transient synchronization security boundaries is developed for a grid-following (GFL)/grid-gorming (GFM) hybrid renewable-energy station comprising GFL wind energy and GFM energy storage. The control objective is to suppress disturbance-induced departures from the dynamic balance between generation-side support and grid/load demand, which are referred to here as power asymmetry rather than phase-domain three-phase imbalance, and to restore a power-symmetric operating state through coordinated active- and reactive-power support. Reduced-order transient synchronization models are established separately for the GFL phase-locked loop and the GFM virtual synchronous generator without explicitly constructing a transient coupling model between the two converter types. For the GFM converter, damping energy is incorporated into the fault-stage transient-energy balance. The resulting transient-energy functions and critical-energy criteria are used to determine the synchronization-stability boundaries, which are then mapped into dynamically updated P-Q feasible regions. A frequency–voltage prediction model combining a system frequency-response model and a point-of-common-coupling voltage-sensitivity model is then established. The GFL/GFM transient-energy constraints, dynamic P-Q security regions, power-regulation capability limits, and command-direction constraints are embedded in the receding-horizon optimization to coordinate active- and reactive-power support while preserving transient synchronization security. Local linearization of the transient-energy constraints and second-order-cone reformulation of the dynamic P-Q regions are adopted to improve online computational efficiency. Simulation results show that, compared with MPC without transient synchronization security boundaries, the proposed strategy limits power-angle excursions, enhances active- and reactive-power support, and mitigates frequency and voltage deviations. A sensitivity analysis is further conducted to examine how uncertainties in grid impedance, inertia, damping, and filter inductance affect the calculated critical energies and P-Q security regions. The results highlight the distinct effects of these parameters on the critical-energy thresholds and dynamic energy margins.